The PT30-10 Mk3 Test Set conducts tests on installed cable and jointing systems. It offers a variable output voltage of up to ±30kVdc and a maximum charging capability of 10mA. It features a zero-volt interlock that prevents switching on the output unless the output control is at zero. Additionally, an automatic load discharge system safely discharges the cable under test when switching off the output or in case of a breakdown.
The PT30-10 Mk3 comes standard with a manual DP40 discharge probe, enabling safe discharge of higher load capacitances. It also introduces automatic 115/230V mains voltage selection for seamless transition between site voltages.
±30kVdc output voltage
10mA output capability
Both voltage and current metered on HV output
Automatic earth system for dumping capacitive loads
HV output plug & socket
Key operated supply switch to prevent unauthorised operation
Zero-volt interlock
Zero-volt interlock
Visual indication of test piece failure